Microflex is the only two part loop powered transmitter with a separate visual display, which enables total flexibility when installing and commissioning this simple level controller. The transducer can be mounted over the vessel or tank while the simple program setup can be carried out safely with both feet on the ground. This system can also be calibrated with full, empty or part empty vessels and does not require any additional moving of the transducer or emptying and filling of the tanks.

A display of the operating parameters is also available at the touch of a button for the milliamp output, distance, level, echo confidence and temperature of the transducer.

 

PERFORMANCE SPECIFICATION
Measuring principle Non-contact Ultrasonic
Measuring range 6 Metres maximum on liquids
Measuring modes Level or distance
Accuracy of change in level -/+ 0.25% of measured distance
Resolution 2mm or 0.1% of empty distance
(whichever is greater)
Damping Adjustable
Blanking Adjustable
   
HARDWARE SPECIFICATION
Power supply 20-30 VDC
Analogue output 4-20 mA \ 12 bit \Loop Powered
Ambient Temperature -40 to + 70Deg C
Display 4 digit 12mm LCD
Interface 5 Push buttons
Temperature compensation Integral in RZT Transducer / IP68
Enclosure IP65 Polycarbonate 170x120x55mm
Approvals Certified EExm ll T6 Transducer (Zones 1 and 2)

home  level   flow  temperature  pressure  CO2 monitor   distributors  contact   legal

E-mail: sales@hycontrol.com

Hycontrol's policy is one of continuous development, consequently the right is reserved to modify any specifications without notice.