top

 
 
 
 

PRODUCT INTRODUCTION

The Hycontrol range of Admittance level switches provide simple, accurate and reliable level
control for a wide range of applications. They are suitable for use on liquids, solids, slurries,
pastes, granules, powders and pellets in high temperature, high pressure and corrosive
environments.
The main advantage offered by using this admittance range of switches is their ability to totally
ignore product build up on the sensing probe.
This unique design utilises a protective insulation electrode between the conventional main
electrode and the grounding sleeve which enables the electronics to distinguish between
coatings and actual product level.
This technology also provides an ideal solution for interface detection applications such as oil
on water and liquid detection underneath a layer of foam.
SWITCH FEATURES
Unaffected by material coating on the sensing probe
No moving parts to wear out
Easy installation through a 1” BSP process fitting
High corrosion and chemical resistance as standard options
Universal mounting for high or low level detection
Multiple versions with rod and cable to simplify mounting options
High temperature versions available
Low maintenance technology with no moving parts
Hazardous area certified versions ATEX approved
Adjustable sensitivity for a wide range of products
Adjustable time delay to stop spurious signals from surface ripple
Remote electronics option for high vibration applications
Interface level detection
High and low failsafe selection options
 
TYPICAL APPLICATIONS
Acid Tanks and silos
Bitumen, Tar and Asphalt
Adhesives, Polymers and Paints
Syrups and pastes
Powders ,flakes and granules
 
CONSTRUCTION & APPLICATION
Construction
1.
Main Contact Probe:
SUS304 or SUS316 Material
2.
Main Insulation Probe:
Insulation of main Probe and reference
current, made of either PTFE or PFA.
3.
Reference Current:
Conductive metal probe to dissipate
any possible presence of false signal.
4.
Insulation Probe:
To protect contact probe and external
insulation probe, having very low
current inducing characteristics and is
made of either PTFE or PFA.
5.
Process Connection:
1"BSP (Standard model)
6.
Housing:
Aluminum Alloy with paint finish

7.

Electrical Entry:
1/2" NPT
8.
Housing seal:
Buna N ‘O’ Ring
9.
Time Delay:
FSH and FSL, Time Delay Adjustable
function
10.
Housing Cover:
Aluminum Alloy Spray Paint
 
Industry Applications
Brewery Plant
Mining Plant
Chemical Plant
Paper Manufacturing Plant
Cement Plant
Medical Plant
Coal Plant
Power Plant
Food Processing Plant
Water and Waste Water
Flour Mill
Treatment Plant
Glass Industry
Tar Factory
Paint Plant
Beverage Plant
Plastics Plant
Bitumen Coating Plant
Quarrying Plant
Dairy Plant
Aggregate Plant
Automotive Plant
SPECIFICATION
 
Dimension
(mm)
Model.
MD 11 [Standard Model]
MD 12 [Standard L Type]
MD 20 [Hi-Temp Model]
MD 1280 [ Hi-TempModel]
Operating Temp.
-40 150°C °~
40°C 232°C ~
-40°C 550°C ~
Ambition Temp.
-40°C 65°C ~
-40°C 65°C ~
-40°C 65°C ~
Housing
Aluminium (IP65)
Aluminium (IP65)
Aluminium (IP65)
ProbeMaterial
304SS or 316SS
304SS or 316SS
304SS or 316SS
Insulation
PTFE or PFA
PTFE or PFA
Ceramic
Connection
3/4" BSP
1" BSP
1-1/4" BSP
Sensitivity
0.3PF
0.3PF
0.3PF
Supply Voltage
110/220VAC 10% +
50/60HZ
110/220VAC 10% +
50/60HZ
110/220VAC 10% +
50/60HZ
Power Consumption
3~5 W
3~5 W
3~5 W
Contact Rating
5A/250VAC, DPDT
5A/250VAC, DPDT
5A/250VAC, DPDT
Delay Time
0~90 sec
0~90 sec
0~90 sec
Fail safe mode
High / low
Selectable
High / low
Selectable
High / low
Selectable
Conduit
1/2" NPT x2 hole
1/2" NPT x2 hole
1/2" NPT x2 hole
Operation Pressure
20kg/cm2
20kg/cm2
20kg/cm2
Weight
1.7kg
3.5kg
4.2kg
SPECIFICATION
 
Dimension
(mm)
Model.
MD49 [Separation Model]
MD50 [CableModel]
MD60 [Mini Model]
Operating Temp.
-40°C 150°C,MAX 550°C ~
-40°C 150°C ~
-40°C 150°C ~
Ambition Temp.
-40°C 65°C ~
-40°C 65°C ~
-40°C 63°C ~
Housing
Stainless (IP65)
Aluminium (IP65)-seperation
Aluminium (IP65)
Aluminium (IP65)
ProbeMaterial
304SS or 316SS
304SS or 316SS
304SS or 316SS
Insulation
PTFE or PFA
PTFE or PFA
Ceramic
Connection
3/4" BSP
3/4" BSP
3/4" BSP
Sensitivity
0.3PF
0.3PF
0.3PF
Supply Voltage
110/220VAC 10% +
50/60HZ
110/220VAC 10% +
50/60HZ
110/220VAC 10% +
50/60HZ
Power Consumption
2.3 W
2.3 W
2.3 W
Contact Rating
5A/250VAC, DPDT
5A/250VAC, DPDT
5A/250VAC, DPDT
Delay Time
0~90 sec
0~90 sec
0~90 sec
Fail safe mode
High / low
Selectable
High / low
Selectable
High / low
Selectable
Conduit
1/2" NPT x2 hole
0
0
Operation Pressure
20kg/cm2
20kg/cm2
20kg/cm2
Weight
0
Depend on cable length
0
WIRING DIAGRAM

• Ensure the power supply is shut off
• Pull the power lines through the cable inlet into
the housing


• Power supply voltage could be selected at 110V
or 220V, but the live wire must be connected to
their respective terminals, 110V live wire to 110V
terminal, 220V live wire to 220V terminal. The
neutral line can be connected to 0V terminal and
the ground line is to be connected to the GND
terminal


• Relay output connection:
Relay outputs are set at SPDT or DPDT,
maximum switching current and voltage is
5A/250VAC, able to drive small loads such as:
solenoid valves, alarm sirens, etc. Bigger loads
requires larger relay to drive it. The diagrams
below and on the right are common examples of
wiring methods.


Fail safemode :


Fail safe mode is used primarily to detect
malfunction situations. Example: Power
supply disruptions, causing the relay to lose
it's driving voltage, this type of situation is
called fail safe, meaning that in cases of
black out, there will be an alarm signal. The
fail safe mode “FSH" and "FSL" selection is
dependent on the installation position of the
probe, the table below shows the fail safe
conditions of each mode:

ORDER INFORMATION
 
Hycontrol Level switches with this option have an additional pair of terminals provided in the switch head that simply require a push button switch to connect these two terminals together and this is usually mounted at ground level local to the silo fill point.

After pushing this button the circuit is then loaded as if a product has touched the active part of the probe and the electronics (if working correctly) will detect this change in capacitance and activate the relay to change its state. Any audio or visual alarms wired to this relay will then be activated and will continue until the ground level test button is released. If the test is successful then the operator can then proceed to fill the silo, confident that the high alarm will operate if required to do so.

Hycontrol provide a complete alarm and test panel solution for single or multipoint applications however a simple push button can easily be retrofitted to existing panel installations with little or no disruption to the plant operations providing the alarms and sirens already exist!

This ground level test facility is offered as an option on Hycontrol’s range of capacitive, admittance and vibrating level swiches.

 
HYCONTROL LEVEL TECHNOLOGIES
 
 

home  level   flow  temperature  pressure  CO2 monitor   distributors  contact   legal

E-mail: sales@hycontrol.com

Hycontrol's policy is one of continuous development, consequently the right is reserved to modify any specifications without notice.